OCCURRENCE OF COAL-TAR PITCH PARTICLES IN DRINKING WATER (H4328C) - Final Report to the Department of the Environment April 1980 to May 1983
Report No DWI0093

Dec 1983

SUMMARY

The objective of the work outlined in this report was to determine the extent to which drinking water supplies are contaminated with particles of coal-tar pitch derived from pipe linings. The work stemmed from a WRC survey of polycyclic aromatic hydrocarbon levels in British waters in which the possibility emerged that drinking water may be contaminated with particles of coal-tar pitch arising from the linings of iron distribution pipes.

In Great Britain about 60% by length of the distribution pipes laid for the Water Industry are of ductile iron and the majority of these have been coated internally with coal-tar pitch according to BS 4164. Since about 1977 there has been no further use of coal-tar pitch for this purpose.

Such linings, and any derived particles, can contain up to 50% polycyclic aromatic hydrocarbons (PAH), some of which (e.g. benzo[a]pyrene) are carcinogenic.

In late 1975 the matter was reported to the Standing Technical Advisory Committee on Water Quality and subsequently to the Joint Committee on Medical Aspects of water Quality (MAWQ). MAWQ expressed considerable concern about the possibility of particles of lining material, containing very substantial proportions of carcinogens, lodging in the digestive tract and decided that information was needed on the exposure of people to such particles.

The result was that a contract was placed by the Department of the Environment with the Water Research Centre (WRC) for studies on the occurrence of coal-tar pitch particles in drinking water.

The experimental approach adopted was to examine mains deposits and particles collected from tapwater. Attempts were made to develop methods designed to characterise (size, number, chemical composition) individual particles. One such method showed promise (laser microprobe mass analyser) but would require considerable effort and expense to produce a routine method suitable for use in a surveys As a back-up technique particles were extracted with an organic solvent and the extracts analysed by gas chromatography for the presence of PAH indicative of coal-tar pitch. Experimental details are covered by several appendices.

Due to the time needed to develop and test suitable techniques and the slowness of the methods that emerged, a wide survey of drinking waters was not feasible. However, in the limited number of tapwaters examined one sample exhibited high levels of coal tar pitch.

Mains deposits frequently contained relatively massive levels of PAH due to the presence of coal-tar pitch particles. Coal tar pitch particles down to at least 3 æm diameter were detected and one would expect such particles to be "mobile". Clearly, any situation that disturbs the deposits, such as mains renovations etc. could release coal-tar pitch particles in the water. Such situations need to be examined.

Copies of this report may be available as an Acrobat pdf download under the 'Find Completed Research' heading on the DWI website.